Capteur courant non-invasif SCT-013 100A

SENS-SCT013-100A

Capteur courant non-invasif SCT-013 100A

Pince ampèremétrique 100A, sortie AC — monitoring sans coupure circuit.

Technical analysis

The SCT-013 clamp clips around an existing conductor without cutting it: it is the tool for energy measurement on a live cabinet, with no shutdown and no electrician intervention on the power side. The 100 A/1 V variant integrates its burden resistor, so it reads directly on an ESP32 analog input after conditioning (offset + rectification).

Limits: it is a current sensor, not a power sensor — without voltage and phase measurement, you estimate amperes, not real kW (power factor ignored). The 1 % accuracy and the 13 mm window bound its use. For a DC measurement or a circuit you design yourself, the Hall-effect ACS712 is complementary. Non-invasive energy retrofit is detailed in the dedicated article.

Verified specifications

Every figure below is sourced from the manufacturer datasheet.

Type
Split-core current transformer (non-invasive clamp)
Input / output (100A variant)
0–100 A → 0–1 V (built-in burden resistor)
Accuracy / linearity
1 % / 1 %
Frequency range
50 Hz to 1 kHz
Window (max conductor diameter)
≈ 13 mm
Service voltage
phase ≤ 660 V

References & standards

Applicable standards

  • Sécurité TC — The datasheet mandates: voltage-output secondary NOT short-circuited, current-output secondary NOT open (dangerous overvoltage) — a real installation constraint.